O'Brien CAPPAKTM Pre-traced Capillaries can provide significant improvements in measurement performance and reliability versus field tracing and insulating (PAT. PENDING). Bringing you these advantages: - Predictable year-round performance provides improved temperature stability vs. field solution
- Protects capillary from damage and excessive bending at critical junction with seal and transmitter
- Water-proof outer jacket ensures all components are kept dry and free from mechanical damage during routing and final hook-ups
Types of Pre-Traced Capillaries: - Insulated Solution Minimizes Drift:
- Guaranteed maximum temperature shift on capillary of 30°C over an 80° ambient shift
- At -40°C ambient temperature of the capillary will be greater than 30°C
- +40°C the temperature of the capillary will be less than 60°C
- No external temperature control required
- Uninsulated Solution Reduces Sluggish Response:
- Guaranteed maximum temperature shift on capillary of 48°C over a 80° ambient shift
- Maintain capillary temperature above 6°C at - 40°C ambient
- Capillary will not exceed 50°C at +40°C ambient
- No external temperature control required
- SensorTube™(PAT. PENDING) with Heatpak Enclosure Eliminates Temperature Effects on Capillary and Transmitter:
- Maintain capillary at 50°C ±1°C
- Choose capillary diameter for fastest response
- Choose diaphragm size for fastest response
- Choose fill fluid for fastest response
For additional information on the O'Brien CAPPAKTM contact your Spartan Controls representative. O'Brien CAPPAKTM Pre-Traced Capillaries Brochure
|